首页> 外文期刊>Fire Safety Journal >Fire tests to evaluate CPVC pipe sprinkler systems without fire resistance barriers
【24h】

Fire tests to evaluate CPVC pipe sprinkler systems without fire resistance barriers

机译:通过防火测试评估无防火屏障的CPVC管道喷水灭火系统

获取原文
获取原文并翻译 | 示例
           

摘要

Nine full-scale fire tests were conducted to assess the adequacy of exposed chlorinated poly vinyl chloride (CPVC) pipe and fitting sprinkler systems installed in light hazard occupancies. The tests were conducted in an enclosure using six different types of automatic sprinklers including QREC pendent and sidewall sprinklers, a pendent residential sprinkler, and a sidewall residential sprinkler. Two types of fires, fast growing and slow growing, were used as test fires. The sprinkler in each test was operated with the normal operation pressure until the test fire was almost completely suppressed. Next, to assess the integrity of piping systems after fire exposure, the water pressure was increased to 12.1 bar and maintained for 10 min and then were visually inspected for any leakage while hydrostatic pressure was maintained at 12.1 bar. No leakage was detected in any of the tests. The results of the tests indicate that sprinkler systems based on exposed CPVC pipe and fittings can be safely installed in light hazard occupancies and will provide adequate protection when installed to all the relevant standards.
机译:进行了九次全面的火灾测试,以评估暴露在轻度危险场所的暴露的氯化聚氯乙烯(CPVC)管道和配件洒水系统的适当性。该测试是在一个封闭的环境中使用六种不同类型的自动洒水器进行的,这些自动洒水器包括QREC侧喷式和侧喷式喷头,侧喷式住宅式喷淋头和侧墙式家用喷头。两种类型的火灾(快速增长和缓慢增长)被用作测试火灾。每个测试中的洒水喷头均以正常工作压力运行,直到测试火几乎被完全抑制为止。接下来,为评估火灾后管道系统的完整性,将水压升至12.1 bar,并保持10分钟,然后目视检查是否有渗漏,同时静水压保持在12.1 bar。在任何测试中均未检测到泄漏。测试结果表明,以裸露的CPVC管和配件为基础的洒水装置可以安全地安装在轻度危险场所,并且在按照所有相关标准安装时将提供足够的保护。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号