A non-dimensional criterion and its proof for transient flow caused by fire in ventilation network

机译:通风网络中火灾引起的瞬态流动的无量纲准则及其证明

获取原文
获取原文并翻译 | 示例
           

摘要

Application of ID Transient Flow Model to a network analysis finds that the fluids in two branches (which are connected in parallel and contain no drive source) may no longer flow in a same direction while the network flow state changes from being steady into being unsteady due to a fire in the ventilation network. This phenomenon can be referred to as non-parallel flows in parallel branches. A non-dimensional criterion ξ is deduced theoretically. It is proved that for any two branches which are connected in parallel and contain no drive source, Non-parallel flows can be expected in the branches only if ξ is not equal to unity. If ξ is equal to unity, the non-dimensional flow velocities in the two branches will always be equal to each other. If ξ is not equal to unity, a prediction can be made on which one of the non-dimensional velocities in the two parallel branches will change more rapidly.
机译:ID瞬变流模型在网络分析中的应用发现,当网络流动状态从稳定变为不稳定时,两个分支(并联连接且不包含驱动源)中的流体可能不再朝同一方向流动。在通风网络中起火。这种现象可以称为并行分支中的非并行流。从理论上推导出无量纲准则ξ。事实证明,对于任何两个并联连接且不包含驱动源的分支,只有在ξ不等于1的情况下,才能在这些分支中实现非并行流量。如果ξ等于1,则两个分支中的无量纲流速将始终彼此相等。如果ξ不等于1,则可以预测两个平行分支中的无量纲速度之一将变化得更快。