首页> 外文期刊>Experimental Heat Transfer >Implementation of Liquid Crystal Thermography to Determine Wall Temperatures and Heat Transfer Coefficients in a Tube-in-tube Heat Exchanger
【24h】

Implementation of Liquid Crystal Thermography to Determine Wall Temperatures and Heat Transfer Coefficients in a Tube-in-tube Heat Exchanger

机译:实施管内换热器的液晶热成像技术来确定壁温和传热系数

获取原文
获取原文并翻译 | 示例
       

摘要

Liquid crystal thermography was used in a water-operated concentric tube-in-tube heat exchanger to determine local annular heat transfer coefficients at the inlet region. An annular diameter ratio of 0.54 was considered with the inlet and outlet orientated perpendicularly to the axial flow direction. Both heated and cooled cases were considered at annular Reynolds numbers ranging from 1,000 to 13,800. Wall temperature distributions were directly measured by means of a coating of thermo-chromic liquid crystals. Local heat transfer coefficients at the inlet were higher than those predicted by most correlations, but good agreement was obtained with some literature.
机译:在水操作同心管内换热器中使用液晶热成像法,以确定入口区域的局部环形传热系数。考虑到环形直径比为0.54,入口和出口垂直于轴向流动方向。加热和冷却的情况都被认为是环形雷诺数,范围从1,000到13,800。壁温度分布是通过热致变色液晶涂层直接测量的。进口处的局部传热系数高于大多数相关性所预测的系数,但与一些文献获得了很好的一致性。