Heavy current bushings passing through steel cover plates and housing walls of power transformers, generators and other large power equipment are thermally hazardous elements of construction and a source of additional power losses. The safety and reliability of such expensive objects and the safety of power delivery often depend on the proper design of these elements. A computer analysis, based on Maxwell equations and analytical representation of electromagnetic field has been carried out. The nonlinear permeability of solid steel was considered using an analytical approximation. Eddy current losses have been calculated and compared using different experimental and calculation methods. Electromagnetic criteria were used to forecast possible excessive heating and hot spots. Various constructional means of loss and hot spot reduction were considered.
机译:穿过钢制盖板和电力变压器,发电机及其他大型电力设备的壳体壁的大电流套管是热危险的结构要素,也是造成额外功率损失的原因。这种昂贵物体的安全性和可靠性以及电力输送的安全性通常取决于这些元件的正确设计。已经基于麦克斯韦方程和电磁场的解析表示进行了计算机分析。使用解析近似法考虑了实心钢的非线性渗透率。已经使用不同的实验和计算方法计算并比较了涡流损耗。电磁标准用于预测可能的过度加热和热点。考虑了各种结构上的损耗和热点减少方法。