Power balance control of micro gas turbine generation system based on supercapacitor energy storage

机译:基于超级电容器储能的微型燃气轮机发电系统的功率平衡控制

获取原文
获取原文并翻译 | 示例
           

摘要

In view of the impact load problems in the traditional micro gas turbine (MT) power generation system, this paper analyzes its working mechanism and finds the reason lies in the slow response of the micro turbine output power adjustment. In order to make up for the shortage of the instantaneous output power of micro turbine, the method of instantaneous power fast control is proposed. Control algorithm of instantaneous compensation power is raised by power response prediction of MT. The high power dynamic response of super-capacitor energy storage can compensate low dynamic response problem of MT output power, so the instantaneous power of the system is real balance to ensure that the DC bus voltage is smooth and adaptability of MT power generation system is enhanced for impact load. Finally, the correctness" and feasibility of the proposed control strategy are verified by simulation results. (C) 2016 Elsevier Ltd. All rights reserved.
机译:针对传统微型燃气轮机发电系统的冲击负荷问题,分析了其工作机理,发现其原因在于微型燃气轮机输出功率调节的响应较慢。为了弥补微型涡轮机瞬时输出功率的不足,提出了瞬时功率快速控制的方法。通过MT的功率响应预测,提出了瞬时补偿功率的控制算法。超级电容器储能的大功率动态响应可以补偿MT输出功率的低动态响应问题,因此系统的瞬时功率是真正平衡的,以确保直流母线电压平稳,并增强了MT发电系统的适应性冲击载荷。最后,通过仿真结果验证了所提出控制策略的正确性和可行性。(C)2016 Elsevier Ltd.保留所有权利。