Geocooling and thermal energy storage (TES) are two strategies that could help alleviate the energy and carbon emission burden from cooling commercial buildings. This simulation study analyses the potential for geocooling, both with and without TES, in a Mediterranean climate. Spherically-encapsulated phase change material (PCM) was used as the thermal storage medium in the TES system. A PCM TES tank model was developed and validated within the TRNSYS environment. Using a small, lightweight commercial building as a case study, it was found that electricity savings of between 24 and 45% are possible from combining geocooling with TES, when compared to a system based on a reference ground-source heat pump (GSHP). (C) 2017 Elsevier Ltd. All rights reserved.
机译:地热和热能存储(TES)是两种策略,可以帮助减轻商业建筑的能耗和碳排放负担。这项模拟研究分析了在有和没有TES的情况下在地中海气候中进行地冷的可能性。球形封装的相变材料(PCM)被用作TES系统中的储热介质。在TRNSYS环境中开发并验证了PCM TES储罐模型。与基于参考地源热泵(GSHP)的系统相比,使用小型轻巧的商业建筑作为案例研究,发现将地冷与TES结合可以节省24%到45%的电量。 (C)2017 Elsevier Ltd.保留所有权利。