首页> 外文期刊>Energy education science and technology >Transient stability investigation of a power system with multiple SVC and TCSC
【24h】

Transient stability investigation of a power system with multiple SVC and TCSC

机译:具有多个SVC和TCSC的电力系统的暂态稳定性研究

获取原文
获取原文并翻译 | 示例
       

摘要

In this paper, the impact of multiple shunt and series compensators on transient stability of a power system is investigated. Modeling and analysis of a real based multi machine-22 bus system with Static Var Compensator (SVG) and Thyristor Controller Series compensator (TCSC) are performed. The location of the compensators is determined based on the weak buses and transmission lines with the highest voltage drop in the system. Transient stability effects are analyzed for three system cases, one without compensators, one with one compensator at a time and the last one with multiple compensators. Angle and angular speed of rotors, voltage variations at each bus are observed. The simulation results showed that the system with multiple compensators can damp oscillations more effectively.
机译:本文研究了多路并联和串联补偿器对电力系统暂态稳定性的影响。使用静态无功补偿器(SVG)和晶闸管控制器系列补偿器(TCSC)对基于实际的多机22总线系统进行建模和分析。补偿器的位置是根据系统中电压降最高的弱总线和传输线确定的。分析了三种系统情况的瞬态稳定性影响,一种是不带补偿器的情况,一种是一次带一个补偿器的情况,最后一种是带多个补偿器的情况。观察转子的角和角速度,观察每个母线的电压变化。仿真结果表明,具有多个补偿器的系统可以更有效地阻尼振荡。