首页> 外文期刊>Energy Conversion & Management >Experimental Study On The Thermal Performance Of A Mechanical Cooling Tower With Different Drift Eliminators
【24h】

Experimental Study On The Thermal Performance Of A Mechanical Cooling Tower With Different Drift Eliminators

机译:机械式冷却塔的不同除水器热性能试验研究

获取原文
获取原文并翻译 | 示例
           

摘要

Cooling towers are equipment devices commonly used to dissipate heat from power generation units, water-cooled refrigeration, air conditioning and industrial processes. Water drift emitted from cooling towers is objectionable for several reasons, mainly due to human health hazards. It is common practice to fit drift eliminators to cooling towers in order to minimize water loss from the system. It is foreseeable that the characteristics of the installed drift eliminators, like their pressure drop, affect the thermal performance of the cooling tower. However, no references regarding this fact have been found in the reviewed bibliography. This paper studies the thermal performance of a forced draft counter-flow wet cooling tower fitted with different drift eliminators for a wide range of air and water mass flow rates. The data registered in the experimental set-up were employed to obtain correlations of the tower characteristic, which defines the cooling tower's thermal performance. The outlet water temperature predicted by these correlations was compared with the experimentally registered values obtaining a maximum difference of ±3%.
机译:冷却塔是通常用于散发发电设备,水冷制冷,空调和工业过程中的热量的设备。冷却塔散发出的水漂是令人讨厌的,原因有几个,主要是由于对人体健康的危害。通常的做法是将除水器安装到冷却塔上,以最大程度地减少系统的水分流失。可以预见,已安装的除水器的特性(如其压降)会影响冷却塔的热性能。但是,在已复习的书目中未找到有关此事实的参考。本文研究了装有不同除水器的强制通风逆流湿式冷却塔在大范围的空气和水质量流量下的热性能。实验设置中记录的数据用于获得塔架特性的相关性,该特性定义了冷却塔的热性能。将这些相关性预测的出水温度与实验记录的值进行比较,得出最大差值为±3%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号