The Murray Hydroelectric Project, a two-unit, 39 MW total rated capacity, run-of-the-river facility located on the Arkansas River, is described. The emphasis of the paper is on the project's electrical features. The two generating units are of an open-pit design with horizontal double-regulated turbines. Turbine rated speed in 46 RPM. The generator is rated 22.77 MW at a power factor of 0.9. The rated voltage is 6.9 kV. The author also discusses the plant's mechanical-hydraulic governor, its electrical system, a 5.7 mile (9.2l-km), 115 kV transmission line, the plant's black-start capability, its mechanical systems, and the plant, unit, and offsite control systems.
机译:描述了位于阿肯色河上的两台机组,总额定容量39兆瓦的默里水力发电项目。本文的重点是该项目的电气特性。两个发电机组采用露天设计,带有水平双调节涡轮机。涡轮额定转速为46 RPM。发电机的额定功率因子为0.9,额定功率为22.77 MW。额定电压为6.9 kV。作者还讨论了工厂的机械液压调速器,电气系统,5.7英里(9.2l-km),115 kV输电线路,工厂的黑启动能力,其机械系统以及工厂,单位和现场控制系统。