摘要

This paper presents results of simulation studies of the influence of methods of grounding the stator winding of the unit-connected generator neutral on the operating conditions of a 100-percent ground-fault protection excited by the third-harmonic voltage ratio in the generator neutral and at its terminals. The analysis was performed for a generator with the neutral grounded through a ground-fault neutralizer, a third-harmonic stop filter, a resistor, and a capacitive voltage divider. The influence of the parameters of the particular elements of the grounding circuits on the voltage-feeding measuring element of the protection was determined. The capacitance to ground of the generator breakers was taken into account. The simulations were run for 1110-MVA unit-connected generator at ground faults along the whole length of the generator stator winding. It has been found that the method of grounding the generator neutral and the parameter of the grounding elements significantly influences the operating conditions of this protection. It is shown that through the proper selection of these parameters, the ground-fault protection of whole stator winding, counting from the generator neutral to the terminals is ensured.
机译:本文给出了仿真结果,仿真结果表明,将发电机中性点的定子绕组接地方法对发电机中性点的三次谐波电压比所激发的100%接地故障保护的运行条件的影响。在其终端。对发电机进行了分析,该发电机的中性点通过接地故障中和器,三次谐波停止滤波器,电阻器和电容分压器接地。确定了接地电路特定元件的参数对保护装置的馈电测量元件的影响。考虑了发电机断路器的接地电容。对于1110-MVA单元连接的发电机,在接地故障时沿着发电机定子绕组的整个长度进行了仿真。已经发现,将发电机中性点接地的方法和接地元件的参数会显着影响该保护的工作条件。结果表明,通过适当选择这些参数,可以确保整个定子绕组的接地故障保护(从发电机中性点到端子的数量)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号