Control of CO_2 in a naturally ventilated classroom

机译:在自然通风的教室中控制CO_2

获取原文
获取原文并翻译 | 示例
       

摘要

The ventilation performance of a naturally ventilated classroom was investigated to monitor the CO_2 levels and compare compliance with new guidelines. Measurements of CO_2 levels were taken for 1 week during the heating season while different ventilation modes were investigated. The classroom was shown to have adequate ventilation to provide compliance with current recommendations although thermal comfort was sometimes compromised. Trickle ventilation provided useful ventilation at a rate of 0.75 1 s~(-1) per person. Purge ventilation was shown to reduce the CO_2 concentration by 1000 ppm but would not be sufficient to maintain an acceptable level. Experimental measurements showed that the trickle ventilators provided useful background ventilation at a total classroom rate of 22.91 s~(-1) or approximately 0.75 1 s~(-1) per person which is not enough on its own. Night time use of trickle ventilators for reducing day time CO_2 concentration level is not beneficial since the classroom returns to ambient concentration levels by the time the room is used again. Hence energy savings could be made by reducing the overnight background ventilation during heating period. The teaching staff and pupils control the ventilation into the classrooms by thermal comfort rather than air quality.
机译:对自然通风教室的通风性能进行了调查,以监测CO_2的水平,并与新准则进行比较。在采暖季节的1周内测量了CO_2的含量,同时研究了不同的通风方式。教室被证明有足够的通风,可以满足当前的建议,尽管有时热舒适性受到损害。 ckle流通气以每人0.75 1 s〜(-1)的速率提供了有用的通气。已显示吹扫通风可将CO_2浓度降低1000 ppm,但不足以维持可接受的水平。实验测量表明,the流式呼吸机以每人22.91 s〜(-1)或大约0.75 1 s〜(-1)的总教室速率提供了有用的背景通风,这本身是不够的。夜间使用滴流式通风机降低白天的CO_2浓度水平无益,因为教室在再次使用房间时会恢复到环境浓度水平。因此,可以通过减少加热期间的夜间背景通风来节省能源。教学人员和学生通过热舒适而非空气质量来控制进入教室的通风。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号