首页> 外文期刊>Energy and Buildings >Lighting energy savings in offices using different control systems and their real consumption
【24h】

Lighting energy savings in offices using different control systems and their real consumption

机译:使用不同控制系统的办公室的照明节能及其实际消耗

获取原文
获取原文并翻译 | 示例
       

摘要

This paper compares the potential of lighting energy savings in office rooms by using different control systems, for three locations in Europe and the four main orientations. The method is based on DAYSIM simulations to perform daylight calculations, on laboratory measurement to evaluate precise system energy consumptions and on the implementation of a new algorithm to simulate a close-loop daylight dimming system. It appears that the control of the electrical power in function of daylight leads to very high savings; they slightly depend on the room orientation and the location. Savings vary from 45 to 61 %. The performances of an occupancy sensor are also tested. Threshold values of occupancy rate for which daylight dimming leads to higher gains than an occupancy control system vary between 27 and 44% depending on location and orientation. The measurements of the energy consumption of the sensors and detectors also permit to conclude that systems with embedded DALI-compatible ballast controllers should be abandoned in favour of a centralized DALI-compatible ballast controller or embedded analogue systems.
机译:本文针对欧洲的三个地区和四个主要方向,比较了使用不同控制系统的办公室会议室照明节能的潜力。该方法基于DAYSIM仿真以执行日光计算,基于实验室测量以评估精确的系统能耗,以及基于新算法的实施以模拟闭环日光调光系统。看来,根据日光来控制电功率可以节省很多钱。它们在某种程度上取决于房间的方向和位置。节省幅度为45%至61%。还对占用传感器的性能进行了测试。与位置控制系统相比,日光调暗导致更高增益的占用率阈值在27%至44%之间变化,具体取决于位置和方向。传感器和检测器能耗的测量结果还可以得出结论,应该放弃具有嵌入式DALI兼容镇流器控制器的系统,而应该使用集中式DALI兼容镇流器控制器或嵌入式模拟系统。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号