首页> 外文期刊>Energy and Buildings >Simulation of a VAV air conditioning system in an existing building for the cooling mode
【24h】

Simulation of a VAV air conditioning system in an existing building for the cooling mode

机译:在现有建筑物中模拟VAV空调系统的制冷模式

获取原文
获取原文并翻译 | 示例
       

摘要

In this study, simulation of a variable air volume (VAV) air conditioning system in an existing office building is presented for the cooling mode. A building simulation package was used for the simulation (DOE, EnergyPlus Engineering Document, Version 1.3., U.S. Department of Energy, Washington, DC, 2005]. The design information of the existing office building, the actual number of the internal load sources such as occupants, lighting, office equipments and the manufacturer's data for the existing rooftop unit (RTU) and the VAV boxes were used in the building simulation package. The simulation results; RTU power consumption, indoor zone temperature and relative humidity, were validated with the data obtained from the on-site measurements performed in the existing office building under the same outdoor conditions. It was found that 71.1% of all simulated power consumption data falls within ± 15% range from the experimental data. The reason for the existence of some data out of band is due to the possible errors associated with the difference in the solar data used for the location 40 km away from the experimental location. It was found that 90.6-94.7% of the indoor temperature experimental data fall within ±1.5 C range from the simulated data, and 88.3-91.3% of the indoor relative humidity data fall within ± 18% range from the simulated data.
机译:在这项研究中,针对制冷模式,对现有办公大楼中的可变风量(VAV)空调系统进行了仿真。使用建筑物模拟包进行模拟(DOE,EnergyPlus工程文档,版本1.3,美国能源部,华盛顿特区,2005年),现有办公楼的设计信息,内部负载源的实际数量,例如在建筑模拟软件包中使用了居住者,照明,办公设备以及现有屋顶单元(RTU)和VAV盒的制造商数据,并通过以下方法验证了模拟结果; RTU功耗,室内区域温度和相对湿度。数据是从在相同室外条件下在现有办公楼中进行的现场测量获得的,发现所有模拟功耗数据中的71.1%都在实验数据的±15%范围内。带外数据是由于与距实验位置40 km的位置所用的太阳能数据差异有关的可能误差所致。发现90.6-94.7%的室内温度实验数据在模拟数据的±1.5 C范围内,88.3-91.3%的室内相对湿度数据在模拟数据的±18%范围内。

著录项

  • 来源
    《Energy and Buildings》 |2009年第9期|922-929|共8页
  • 作者单位

    Center for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, 3163 Glenn Martin Hall Bldg., College Park, MD 20742, USA;

    Center for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, 3163 Glenn Martin Hall Bldg., College Park, MD 20742, USA;

    Center for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, 3163 Glenn Martin Hall Bldg., College Park, MD 20742, USA;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    VAV; RTU; air conditioning; simulation; cooling; office;

    机译:VAV;RTU;空调;模拟;冷却;办公室;
  • 入库时间 2022-08-18 00:10:32