The response of a complex Data Centre chilled water system to an unplanned site-wide power failure and the influence on the Data halls

机译:复杂的数据中心冷冻水系统对计划外的站点范围内的电源故障的响应以及对数据大厅的影响

获取原文
获取原文并翻译 | 示例
           

摘要

The paper describes the modelling and analysis of a 10 MW chilled water distribution system that is used for the cooling of parallel Data halls. During an unplanned site power failure, the Chillers may go offline for some minutes, affecting the temperature and delivery of chilled water to the Data hall cooling units. This may cause the air temperature within the Data halls to rise. The ultimate test of robustness is to ensure that the IT equipment is adequately cooled during this time. This work outlines the key findings from the thermal response of the cooling system to a site power failure. The entire chilled water network that comprised the primary and secondary plant was modelled, including components such as pumps, valves and Chillers. A transient analysis was conducted to predict the rise in water temperature at different locations in the system. Computational fluid dynamics was then adopted to predict the air temperature reaching the IT equipment, therefore confirming the capability of the design to steer clear of effects such as thermal runaway.The findings demonstrate that confidence in the omission of expensive buffer vessels and UPS backed plant could not have been achieved without the advanced transient analysis conducted here.
机译:本文介绍了用于并行数据大厅冷却的10 MW冷冻水分配系统的建模和分析。在计划外的站点电源故障期间,冷水机组可能会离线运行几分钟,从而影响温度以及将冷水输送到数据厅冷却装置的情况。这可能导致数据大厅内的空气温度升高。耐用性的最终测试是确保在此期间IT设备得到充分冷却。这项工作概述了冷却系统对现场电源故障的热响应的主要发现。对包括主要工厂和次要工厂的整个冷冻水网络进行了建模,包括泵,阀门和冷却器等组件。进行了瞬态分析,以预测系统中不同位置的水温升高。然后采用计算流体动力学来预测到达IT设备的空气温度,因此证实了设计能够避免诸如热失控之类的影响的结果,结果表明,人们对省略昂贵的缓冲容器和UPS支持的工厂的信心可以如果不进行此处的高级瞬态分析,则无法实现。

著录项

  • 来源
    《Energy and Buildings》 |2010年第10期|P.1736-1746|共11页
  • 作者单位

    Cundall LLP, Saffron House, 6-10 Kirby Street, London EC1N 8TS, United Kingdom;

    rnCundall LLP, Saffron House, 6-10 Kirby Street, London EC1N 8TS, United Kingdom;

    rnCundall LLP, Saffron House, 6-10 Kirby Street, London EC1N 8TS, United Kingdom;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    data centre; chilled water system; power failure; computational fluid dynamics;

    机译:数据中心;冷冻水系统;电源(检测)失败;计算流体动力学;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号