This paper analyzes the performance of a novel two-pipe system that operates one water loop to simultaneously provide space heating and cooling with a water supply temperature of around 22 degrees C. To analyze the energy performance of the system, a simulation-based research was conducted. The two-pipe system was modelled using the equation-based Modelica modeling language in Dymola. A typical office building model was considered as the case study. Simulations were run for two construction sets of the building envelope and two conditions related to inter-zone air flows. To calculate energy savings, a conventional four-pipe system was modelled and used for comparison. The conventional system presented two separated water loops for heating and cooling with supply temperatures of 45 degrees C and 14 degrees C, respectively. Simulation results showed that the two-pipe system was able to use less energy than the four-pipe system thanks to three effects: useful heat transfer from warm to cold zones, higher free cooling potential and higher efficiency of the heat pump. In particular, the two-pipe system used approximately between 12% and 18% less total annual primary energy than the four-pipe system, depending on the simulation case considered. (C) 2016 Elsevier B.V. All rights reserved.
机译:本文分析了一种新型的两管系统的性能,该系统通过一个水循环来同时提供大约22摄氏度的供水温度来提供空间供暖和制冷。为分析系统的能源性能,本文进行了基于仿真的研究进行。两管系统是在Dymola中使用基于方程式的Modelica建模语言建模的。一个典型的办公大楼模型被认为是案例研究。针对建筑物围护结构的两个构造集以及与区域间气流相关的两个条件进行了模拟。为了计算节能量,对传统的四管系统建模并进行比较。常规系统提供了两个分开的水回路,分别用于加热和冷却,供水温度分别为45摄氏度和14摄氏度。仿真结果表明,两管系统比四管系统能消耗更少的能源,这要归功于以下三个方面的影响:从暖区到冷区的有效传热,更高的自然冷却潜能以及更高的热泵效率。尤其是,根据所考虑的模拟情况,两管系统比四管系统的总年度一次能源要少约12%至18%。 (C)2016 Elsevier B.V.保留所有权利。

著录项

  • 来源
    《Energy and Buildings》 |2017年第1期|234-247|共14页
  • 作者单位

    Aalborg Univ, Danish Bldg Res Inst, AC Meyers Vaenge 15, DK-2450 Copenhagen, Denmark;

    Lawrence Berkeley Natl Lab, 1 Cyclotron Rd, Berkeley, CA 94720 USA;

    Aalborg Univ, Danish Bldg Res Inst, AC Meyers Vaenge 15, DK-2450 Copenhagen, Denmark;

    Lindab Comfort AS, Lucernemarken 17, DK-3520 Farum, Denmark;

    Aalborg Univ, Danish Bldg Res Inst, AC Meyers Vaenge 15, DK-2450 Copenhagen, Denmark;

    Lindab Comfort AS, Lucernemarken 17, DK-3520 Farum, Denmark;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Energy saving; HVAC systems; Low-exergy; Simulation; Modelica; Active beams;

    机译:节能;暖通空调系统;低能耗;模拟;Modelica;主动梁;