首页> 外文期刊>Energy and Buildings >Experimental study on thermal buoyancy-induced natural ventilation
【24h】

Experimental study on thermal buoyancy-induced natural ventilation

机译:热浮力自然通风的实验研究

获取原文
获取原文并翻译 | 示例
       

摘要

It is well known that natural ventilation is caused by the outdoor wind velocity and the indoor-outdoor temperature difference. Generally, natural ventilation is rarely caused by one effect alone, but by the coupled form of two effects. However, only the indoor-outdoor temperature difference (AT) was considered to evaluate the characteristic of thermal buoyancy-induced natural ventilation in this experimental study. The indoor-outdoor temperature differences were set to 5, 10, 20 and 30 degrees C. The measured ventilation rates by changing AT were compared to the calculation results based on the hydrostatic theory. From the experimental results, it was found that the ventilation rate is exponentially proportional to AT and the area ratio (AR) of the inlet opening to the outlet opening is an important factor to affect natural ventilation. However, the influence on a ventilation rate by AR nearly disappeared when AR exceeds over 5.0. In addition to it, it was identified that AR and a flow resistance coefficient of Ca for ventilation can be correlated as an exponential function and its form is exp(-3.6AR). (C) 2018 Elsevier B.V. All rights reserved.
机译:众所周知,自然通风是由室外风速和室内外温差引起的。通常,自然通风很少单独由一种作用引起,而是由两种作用的结合形式引起。但是,在本实验研究中,仅考虑室内外温差(AT)来评估由热浮力引起的自然通风的特性。将室内外温差设置为5、10、20和30摄氏度。将通过改变AT测得的通风率与基于静水压理论的计算结果进行比较。从实验结果中发现,通风速率与AT成指数比例,并且进气口与排气口的面积比(AR)是影响自然通风的重要因素。但是,当AR超过5.0时,AR对通气率的影响几乎消失。除此之外,还确定了AR和通风的Ca的流阻系数可以作为指数函数相关,其形式为exp(-3.6AR)。 (C)2018 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号