The relevance of subsequent strokes on the lightning performance of 138-kV lines is assessed. An electromagnetic model was used to simulate lightning overvoltages experienced across insulator strings due to direct strikes to the towers of an existing line in order to determine the critical peak current required to flashover using the integration method. From peak current distributions, estimates of outage rate due to backflashover were developed considering the contribution of first and subsequent strokes. It was found that, depending on the value of tower-footing grounding resistance, the contribution of subsequent strokes can be relevant, notably for tall towers, with height above 30 m.
机译:评估了后续笔划与138 kV线路的雷电性能的相关性。为了确定使用集成方法闪络所需的临界峰值电流,使用了电磁模型来模拟由于直接冲击现有线路的塔而在绝缘子串两端经历的雷电过电压。根据峰值电流分布,考虑了第一个冲程和后续冲程的影响,对由于反闪引起的断电率进行了估算。结果发现,取决于塔底接地电阻的值,后续冲程的贡献可能是相关的,特别是对于高度超过30 m的高层塔架。