TRANSIENTS IN THE CURRENT CIRCUITS OF HIGH-SPEED PROTECTIONS OF THE MAIN EQUIPMENT OF POWER STATIONS UNDER CONDITIONS OF SEQUENTIAL SHORT-CIRCUIT FAULTS

机译:顺序短路故障条件下电站主要设备的高速保护电路中的瞬态变化

获取原文
获取原文并翻译 | 示例
           

摘要

A method of identifying the conditions for extreme spurious signals to occur due to the interaction of current transformers (CT) arranged in three-phase groups when sequential phase-to-ground short-circuit faults occur, is proposed. The method enables the currents in the healthy phases to be taken into account and enables the influence of sequential switching operations on the aperiodic component of the primary and secondary currents to be considered. A maximum aperiodic component can develop when a double sequential short-circuit fault, that is, a single-phase fault - two-phase ground fault - three-phase short-circuit fault, occurs. An extreme distortion of the secondary current of a saturated CT may occur when there is a sequential short-circuit fault and when the CT in the healthy phase in the group of CTs connected in a star become saturated as a result of an excessive zero-sequence current, which is typical for the high-voltage equipment of power stations.
机译:提出了一种在相继发生对地短路故障时,识别由于三相组中的电流互感器(CT)的相互作用而导致极端杂散信号发生的条件的方法。该方法使得可以考虑健康阶段中的电流,并且可以考虑顺序开关操作对一次和二次电流的非周期性分量的影响。当发生两次连续的短路故障,即“单相故障-两相接地故障-三相短路故障”时,会产生最大的非周期性分量。当出现连续的短路故障并且星型连接的一组CT中处于健康状态的CT由于过大的零序而变得饱和时,可能会导致饱和CT的次级电流极端失真。电流,这是电站高压设备的典型特征。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号