摘要

The effects of humidity, for alternating voltages up to about 700 kV r.m.s. and impulse voltages up to about 1500kV, on gaps between 1m spheres, on rod-gaps, on suspension insulators and on pedestal-post insulators are described. Data are given on cylindrical-post insulators with alternating current and on point-plane gaps with impulse voltages. The data are limited but appear to be sufficient to justify conclusions which could affect practice, in particular, it appears that the a.c. flashover voltage of some gaps and insulators falls at high humidities, so that the negative correction in use at present should be replaced by a positive correction. The data for positive impulses, except for the sphere-gap, show that flashover voltages increase continuously with humidity. The effect with negative impulses is in some cases negligible.
机译:湿度的影响,对于最高约700 kV r.m.s的交流电压并描述了在1m球之间的间隙,杆间隙,悬挂绝缘子和立柱支柱绝缘子上高达1500kV的脉冲电压。给出了具有交流电的圆柱支柱绝缘子和具有脉冲电压的点平面间隙的数据。数据有限,但似乎足以证明可能影响实践的结论是正确的,尤其是看来某些间隙和绝缘子的闪络电压在高湿度下会下降,因此目前使用的负校正应由正校正代替。除球形间隙外,正脉冲的数据表明,闪络电压随着湿度的增加而连续增加。在某些情况下,负脉冲的影响可以忽略不计。