首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Transient overvoltages and power-line terminations
【24h】

Transient overvoltages and power-line terminations

机译:瞬态过电压和电源线终端

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The paper outlines an investigation which was initiated to obtain an understanding of the mechanism by which overvoltages, of sufficient magnitude to cause flashover, are produced on a line section which forms part of a 132kV system. The line is terminated at one end with a series-connected inductor; the overvoltage occurs when the line is initially energised by an air circuit breaker at the other end. Basic data regarding the high-frequency performance of current-limiting inductors of different manufacturers have been obtained by measurement on site. This information is used, in conjunction with an estimate of the earth-capacitance distribution along the inductor winding, to obtain a simple equivalent circuit which is representative in the kilocycle-per-second range of frequencies. Owing to lack of access, the line parameters have been estimated from the known characteristics of other lines. The usual approach to a theoretical solution of the problem, by the use of transforms and lattice diagrams, is shown by simple examples to fall short of the requirements when reactive terminations are involved. A new approach, using a Fourier series, is shown to provide the required solutions. This form of analysis is explained in terms of the frequency response of the system, and the results are verified by crosschecking using various line-inductor combinations on a laboratory model. These model tests have also helped to provide an understanding of the action of various independent variables met with on the system, e.g. the effect of changes of source impedance. The results of the analysis and tests indicate that the overvoltage produced may be of the order of five times the peak phase-to-earth voltage of the system. To assist with estimating the probable overvoltages in similar circumstances, a curve has been obtained from a computer, showing the overvoltage against line length for a particular inductor. It is indicated that this method of solution can be used to determine sy-nstem performance where more complicated terminations are used.
机译:本文概述了一项调查工作,该调查工作旨在加深对形成132kV系统一部分的线路部分上产生足以引起闪络的过电压的机理的理解。线路的一端用串联的电感器端接;当线路最初由另一端的空气断路器供电时,就会发生过电压。通过现场测量获得了有关不同制造商的限流电感器的高频性能的基本数据。该信息与沿电感器绕组沿地电容分布的估计值结合使用,可得到一个简单的等效电路,该电路在频率的千分之一秒范围内具有代表性。由于缺少访问权限,已从其他线路的已知特性中估算了线路参数。通过简单的示例显示了通过使用变换和晶格图来解决问题的理论方法的常用方法,无法满足涉及电抗性端接时的要求。显示了一种使用傅立叶级数的新方法来提供所需的解决方案。根据系统的频率响应说明了这种分析形式,并通过在实验室模型上使用各种线路-电感器组合进行交叉检查来验证结果。这些模型测试还有助于提供对系统上遇到的各种自变量的作用的理解,例如源阻抗变化的影响。分析和测试的结果表明,产生的过电压可能约为系统峰值相间电压的五倍。为了在类似情况下帮助估计可能的过电压,已经从计算机获得了一条曲线,显示了特定电感器的过电压与线长的关系。指出在使用更复杂的终端的情况下,这种解决方法可用于确定系统性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号