This paper explains what is believed to be a unique method evolved for protection of a grid network of 37.5-kV transmission lines against line-to-earth faults, which enables automatic selection and isolation of a section subjected to a sustained fault to take place without utilizing earth-fault current for the operation of protective relays, or pilot wires between sectionalizing stations remote from one another. The scheme provides for the installation of Petersen coils together with special automatic selectors and associated equipment, and has been employed with considerable success since 1936 for protection of the Ganges Canal hydro-electric grid in the United Provinces, India.
机译:本文解释了一种被认为是保护37.5 kV输电线路的电网免受线对地故障的独特方法,该方法可以自动选择和隔离遭受持续性故障的区域,而不会发生利用接地故障电流来操作保护继电器,或者在彼此远离的分段站之间进行控制。该方案提供了Petersen线圈的安装以及特殊的自动选择器和相关设备,自1936年以来已成功地用于保护印度联合省的恒河运河水力发电网。