A transformer switching onto a line can sometimes cause a circuit breaker to trip or a fuse to blow. This phenomenon occurs even if the transformer presents no load, such as when the secondary is open. The problem arises because of the heavy magnetizing inrush current in the transformer. The amplitude of the current de-pends on the instant on the ac waveform at which the transformer becomes energized. The inrush current is at its maximum value if the transformer becomes energized when the ac waveform goes through its zero-crossing point. A similar situation exists when a capacitor in a power-factor-improvement bank switches onto the line. In this case, the in-rush current is at its maximum when the ac waveform goes through its peak value. Normally, a mechanical contactor effects the switching with-out any control of the instant of switching.
机译:变压器接入线路有时会导致断路器跳闸或保险丝熔断。即使变压器没有负载,例如次级绕组断开时,也会出现这种现象。由于变压器中大量的励磁涌流而出现问题。电流的幅值取决于交流波形上的瞬间,变压器开始通电。如果当交流波形经过其过零点时变压器通电,则浪涌电流将达到最大值。当功率因数改善组中的电容器切换到线路上时,存在类似情况。在这种情况下,当交流波形通过其峰值时,浪涌电流达到最大值。通常,机械接触器会在不控制切换瞬间的情况下实现切换。