Last month in this space we perused a particular case of a second building on a property and the location of the service disconnecting means. Now we will look at the subject in general. Discussed here is the most common situation of a three-wire 120/240 Volt 10 feeder to the second building, two ungrounded conductors and a neutral conductor, and more than one branch circuit in the second building. Even when leaving the first building as a feeder, the rule for many years was to treat the disconnect and the grounding of the neutral at the second building as if it were a service. A grounding electrode if not existing had to be installed, and the neutral conductor had to be bonded to the grounding electrode conductor and the equipment grounding conductors within the disconnect either inside or outside the building.
机译:上个月,在这个空间中,我们仔细研究了物业上第二座建筑物的特殊情况以及服务断开装置的位置。现在,我们将大致研究该主题。此处讨论的是最常见的情况,即通往第二座建筑物的三线120/240伏10馈线,两条未接地的导线和一条中性导线以及第二座建筑物中的多个分支电路。即使离开第一座建筑物作为馈线,多年的规则仍然是将第二座建筑物的断开连接和中性点接地视为服务。必须安装接地电极(如果不存在),并且必须将中性导体与建筑物内部或外部隔离区内的接地电极导体和设备接地导体相连。