GFCI Receptacles Require an Equipment Grounding Conductor to Be Safe

机译:GFCI插座要求设备接地导体安全

获取原文
获取原文并翻译 | 示例
           

摘要

A Reader Hired An Electrician To install a new circuit for a 120-volt 1Φ window air conditioner in his home, but was later informed by a friend that he could have saved money by simply replacing the existing two-wire receptacle with a ground fault circuit interrupter (GFCI) receptacle. He asked if he did the right thing. He certainly did. There is permission in National Electrical Code(NEC) Section406.3(D)(3)(b) to replace a nongrounding receptacle with a GFCI receptacle, where no grounding means exists in the box, and it requires adding the marking "No Equipment Ground."
机译:一位读者雇了一名电工为他的家中的120伏1Φ窗口式空调安装新电路,但后来被一位朋友告知,只要用接地故障电路替换现有的两线插座,他本可以省钱的灭弧室(GFCI)插座。他问他做对了吗。他当然做到了。国家电气法规(NEC)第406.3(D)(3)(b)条允许用GFCI插座替换不接地的插座,该插座中没有接地装置,并且要求添加标记“无设备”地面。”