Given two three-wire three-phase power circuits, No. 4 cu, in one conduit, Table 310.15(B)(2)(a) requires that the ampacity be limited to 80 percent of that shown in Table 310.16. If the conductors of one of the circuits has 60 C insulation, type TW, the Table 310.16 ampacity is 70 amperes, and the adjustment factor of 80 percent brings the ampacity down to 56 amperes. Per 240.4(B), the overcurrent protection is permitted to be not greater than 60 amperes. The other set of conductors is type THWN with an insulation rating of 75 C and ampacity of 85. Taking the adjustment factor of 80 percent, the ampacity is reduced to 68, with the overcurrent protection at 70 amperes.
机译:给定在一根导管中有两个4 cu的三线三相电源电路,表310.15(B)(2)(a)要求将载流量限制为表310.16所示容量的80%。如果其中一个电路的导体具有TW类型的60 C绝缘,则表310.16的载流量为70安培,调整系数为80%可使载流量降至56安培。根据240.4(B),过流保护允许不大于60安培。另一组导体为THWN型,绝缘额定值为75 C,载流量为85。调整系数为80%,载流量减小到68,过电流保护为70安培。