Insulated ground wire capacitive currents for tower discharge warning lamp supplying

机译:用于塔式放电警告灯的绝缘地线电容电流

获取原文
获取原文并翻译 | 示例

摘要

In order to supply warning discharge lamps installed atop towers, the insulation of ground wires in HV and EHV can be used. The paper describes a simplified yet efficient matrix procedure which allows both to compute the capacitive induced voltages and to determine the equivalent circuit supplying such non-linear loads. In addition, the waveform of the conduction currents and voltages and the average power on the lamps are determined by a fast analytical procedure. The analytical results have been compared with laboratory experimental results giving a really good agreement.
机译:为了提供安装在塔顶的警示放电灯,可以使用HV和EHV中的接地线绝缘。本文介绍了一种简化而有效的矩阵程序,该程序既可以计算电容感应电压,又可以确定提供此类非线性负载的等效电路。另外,通过快速分析程序确定灯的传导电流和电压的波形以及平均功率。将分析结果与实验室实验结果进行了比较,得出了非常好的一致性。