首页> 外文期刊>Electric power systems research >A fault analysis of DC electric arc furnaces with SVC harmonic filters in a mini-mill plant
【24h】

A fault analysis of DC electric arc furnaces with SVC harmonic filters in a mini-mill plant

机译:小型工厂中带有SVC谐波滤波器的直流电弧炉的故障分析

获取原文
获取原文并翻译 | 示例
           

摘要

This paper proposes the most feasible solution to overcome the failure of the 2nd harmonic filter in the static VAR compensator (SVC) which operates with the DC electric arc furnace (EAF) at Gwangyang Steel Mill in Korea. In order to investigate the causes of this failure, various measurements were carried out on the DC EAF and the main transformer at the PCC (point of common connection). It was concluded that the two causes for the failure are; the inrush current in the main transformer, and the parallel resonance between the system impedance and the harmonic filter. Three solutions to suppress the transformer inrush current and another three solutions to avoid the parallel resonance are suggested. The feasibility of these solutions was verified through the computer simulation with PSCAD/EMTDC. The most feasible solution to avoid further failures of the 2nd harmonic filter was selected, based on the estimated result for the six optional solutions in the point of performance and cost.
机译:本文提出了一种最可行的解决方案,以克服与韩国光阳钢铁厂的直流电弧炉(EAF)一起工作的静态无功补偿器(SVC)中的二次谐波滤波器的故障。为了调查此故障的原因,对DC EAF和PCC(公共连接点)上的主变压器进行了各种测量。结论是导致失败的两个原因是:主变压器的涌入电流,以及系统阻抗和谐波滤波器之间的并联谐振。提出了三种抑制变压器浪涌电流的解决方案,以及三种避免并联谐振的解决方案。这些解决方案的可行性通过PSCAD / EMTDC的计算机仿真得到了验证。基于六个可选解决方案在性能和成本方面的估计结果,选择了避免二次谐波滤波器进一步故障的最可行解决方案。