首页> 外文期刊>Electric power systems research >Lightning performance of a real distribution network with focus on transformer protection
【24h】

Lightning performance of a real distribution network with focus on transformer protection

机译:专注于变压器保护的实际配电网络的闪电性能

获取原文
获取原文并翻译 | 示例
           

摘要

The paper applies a Monte Carlo procedure to evaluate the lightning performance of a real medium voltage distribution network, which includes a number of lines, transformer stations and surge protection devices. Such a procedure allows inferring the characteristics of the statistical distributions of lightning originated voltages at any point and at any phase of the network. The analysis presented in this paper aims at assessing the expected mean time between failures of MV/LV transformers caused by both direct and indirect lightning strikes. A heuristic technique has been specifically developed to reduce the computational effort despite the non-linear response of the network equipped with surge arresters. (C) 2015 Elsevier B.V. All rights reserved.
机译:本文应用蒙特卡洛程序来评估实际中压配电网的雷电性能,该网络包括许多线路,变电站和电涌保护装置。这样的过程允许推断在网络的任何点和任何相位的雷电产生的电压的统计分布的特征。本文中提出的分析旨在评估由直接和间接雷击引起的MV / LV变压器故障之间的预期平均时间。尽管配备了避雷器的网络具有非线性响应,但已经专门开发了启发式技术来减少计算量。 (C)2015 Elsevier B.V.保留所有权利。