首页> 外文期刊>Electric power systems research >Transients caused by switching of 420 kV three-phase variable shunt reactor
【24h】

Transients caused by switching of 420 kV three-phase variable shunt reactor

机译:切换420 kV三相可变并联电抗器引起的瞬变

获取原文
获取原文并翻译 | 示例
           

摘要

This paper describes transients caused by uncontrolled and controlled switching of three-phase 420 kV variable shunt reactor (VSR). The model for the analysis of the transients caused by switching of VSR was developed in the EMTP-RV software. It includes a dynamic electric arc in SF6 circuit breaker and the model of substation equipment. Inrush currents due to VSR energization and overvoltages due to deenergization were determined at tap positions corresponding to lowest 80 MVAr and highest 150 MVAr reactive power. Based on the calculation results, mitigation measures and operating switching strategy of VSR were proposed. (C) 2015 Elsevier B.V. All rights reserved.
机译:本文介绍了由三相420 kV可变并联电抗器(VSR)的不受控制的开关控制引起的瞬变。在EMTP-RV软件中开发了用于分析由VSR切换引起的瞬态的模型。它包括SF6断路器中的动态电弧和变电站设备的模型。在对应于最低80 MVAr和最高150 MVAr无功功率的抽头位置确定了由于VSR通电引起的浪涌电流和由于断电引起的过电压。根据计算结果,提出了VSR的缓解措施和运行切换策略。 (C)2015 Elsevier B.V.保留所有权利。