首页> 外文期刊>Electric power systems research >Energization simulations of a half-wavelength transmission line when subject to three-phase faults-Application to a field test situation
【24h】

Energization simulations of a half-wavelength transmission line when subject to three-phase faults-Application to a field test situation

机译:遭受三相故障的半波长传输线的通电仿真-在现场测试中的应用

获取原文
获取原文并翻译 | 示例
           

摘要

The purpose of this paper is to supply technical data for the proposed field energization of 500 kV transmission lines present in the Brazilian interconnected system, forming a line, henceforth called AC-Link, slightly over a half-wavelength in 60 Hz. The purpose of the test is to investigate overvoltages and currents that result from the energization of the AC-Link. This paper shows the results of simulations performed in ATP (Alternative Transients Program) when considering the occurrence of three-phase faults along the AC-Link during energization. The results obtained show that, in certain situations, the overvoltages and energies in the arresters may reach very high values and some specific mitigation procedure should be implemented. (C) 2016 Elsevier B.V. All rights reserved.
机译:本文的目的是为巴西互连系统中建议的500 kV输电线路的现场通电提供技术数据,形成一条线路,此后称为AC-Link,在60 Hz的半波长范围内略微超过一半。该测试的目的是研究由交流链路通电引起的过电压和电流。本文显示了在通电过程中考虑沿AC-Link发生三相故障时在ATP(备用瞬态程序)中进行的仿真结果。获得的结果表明,在某些情况下,避雷器中的过电压和能量可能会达到很高的值,因此应执行一些特定的缓解措施。 (C)2016 Elsevier B.V.保留所有权利。