Fault mode operation strategies for dual H-bridge current flow controller in meshed HVDC grid

机译:HVDC网格中双H桥电流控制器的故障模式操作策略

获取原文
获取原文并翻译 | 示例
       

摘要

Current flow controllers (CFCs) can remove grid bottlenecks or extend grid operation area by changing amount of power flowing through DC transmission lines. This study focuses on behavior of interline El bridge CFC in a DC grid in fault condition. In addition to the CFC circuit level fault studies, non-linear and linearized simplified models are developed for system level analysis. The analysis and fault study shows that the interline H-bridge CFC cannot survive during DC transmission line and bus faults due to an overvoltage occurring in its capacitor. Further investigation figures out that this overvoltage cannot be avoided even in presence of fast HVDC circuit breakers. Hence, an improved control system together with circuit level modifications are proposed to improve the CFC post-fault operation and to retain its components from possible damages. (C) 2018 Published by Elsevier B.V.
机译:电流控制器(CFC)可以通过更改流过直流输电线路的电量来消除电网瓶颈或扩展电网运行范围。这项研究的重点是故障条件下直流电网中线间El桥CFC的行为。除了CFC电路级故障研究之外,还开发了非线性和线性化简化模型用于系统级分析。分析和故障研究表明,线路间H桥CFC在直流传输线和总线故障期间由于其电容器中发生过电压而无法幸存。进一步的研究表明,即使存在快速HVDC断路器,也无法避免这种过电压。因此,提出了一种改进的控制系统以及电路级修改,以改善CFC故障后的操作并保护其组件免受可能的损坏。 (C)2018由Elsevier B.V.发布