首页> 外文期刊>Electric power systems research >A fault ride through strategy of unified power flow controller and its coordination with protection
【24h】

A fault ride through strategy of unified power flow controller and its coordination with protection

机译:通过统一电流控制器的策略及其与保护的协调来实现故障

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

When a fault occurs on the line equipped with Unified Power Flow Controller (UPFC) based on Modular Multilevel Converter (MMC), it may cause the blocking of MMCs and then make UPFC out of operation. To avoid the non-function of UPFC under the condition of external fault, a UPFC fault ride through (FRT) strategy, which can convert UPFC to Static Synchronous Compensator (STATCOM), is proposed. The FRT strategy is realized by connecting the Current Limiting Reactor (CLR) on the DC bus to limit the fault current flowing through the DC bus, which is good for the shunt side MMC being unblocked. On the other hand, the FRT strategy may cause the series side MMC be unblocked under some fault cases, which has adverse effects on the distance protection due to the vibration of the measured impedance. To solve this problem, the coordination of the FRT strategy of UPFC with the distance protection is provided, the High Voltage Breaker (HVB) across the series transformer of UPFC is forced to close if the series side MMC is unblocked during FRT, thus the performance of the distance relay is guaranteed. Simulation results based on PSCAD/EMTDC verify the proposed FRT strategy and coordinationi scheme.
机译:当配备有基于模块化多电平转换器(MMC)的统一电流控制器(UPFC)的线路发生故障时,可能导致MMC的阻塞,然后使UPFC失效。为避免在外部故障条件下避免UPFC的非功能,提出了一种通过(FRT)策略,可以将UPFC转换为静态同步补偿器(Statcom)。通过将电流限制电抗器(CLR)连接在DC总线上限制流过DC总线的故障电流来实现FRT策略,这对于分流侧MMC未铺砌,这是良好的。另一方面,FRT策略可能导致系列侧MMC在一些故障情况下卸下,这对由于测量阻抗的振动而对距离保护具有不利影响。为了解决这个问题,提供了UPFC与距离保护的FRT策略的协调,UPFC系列变压器上的高压断路器(HVB)被强制关闭,如果串联MMC在FRT期间未阻止,因此性能保证距离继电器。基于PSCAD / EMTDC的仿真结果验证了拟议的FRT战略和协调方案。

著录项

  • 来源
    《Electric power systems research》 |2020年第7期|106323.1-106323.8|共8页
  • 作者单位

    North China Elect Power Univ State Key Lab Alternate Elect Power Syst Renewabl Beijing 102206 Peoples R China;

    North China Elect Power Univ State Key Lab Alternate Elect Power Syst Renewabl Beijing 102206 Peoples R China;

    North China Elect Power Univ State Key Lab Alternate Elect Power Syst Renewabl Beijing 102206 Peoples R China;

    North China Elect Power Univ State Key Lab Alternate Elect Power Syst Renewabl Beijing 102206 Peoples R China;

    China Elect Power Res Inst State Key Lab Secur & Energy Saving Beijing 100192 Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Unified power flow controller (UPFC); Fault ride through (FRT); Current limiting reactor (CLR); Distance protection;

    机译:统一电流控制器(UPFC);故障乘坐(FRT);电流限制反应器(CLR);距离保护;