首页> 外文期刊>Electric Power Components and Systems >Impact of Third Harmonic Currents on Magnetic Field Measurements from Distribution Lines
【24h】

Impact of Third Harmonic Currents on Magnetic Field Measurements from Distribution Lines

机译:三次谐波电流对配电线路磁场测量的影响

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

Experimental work was done to validate computed results of magnetic fields from distribution lines with current harmonic distortion. Measurement results agree well with simulation. Results show that the magnetic field could be as much as 35 times greater (total-harmonic distortion (THD) = 20%) if the harmonic distortion is overlooked. We show that a discrepancy occurs between the maximum and resultant definitions of the magnetic field value when the harmonic currents are considered. Furthermore, the paper shows that the variation in phase displacement of the 3rd harmonic current may increase the field at one side while decreasing it on the other side. This, in fact, may help avoid the critical side where field exposure hazards are more likely.
机译:进行了实验工作,以验证具有电流谐波畸变的配电线路磁场的计算结果。测量结果与仿真吻合得很好。结果表明,如果忽略了谐波失真,则磁场可能高达35倍(总谐波失真(THD)= 20%)。我们表明,当考虑谐波电流时,磁场值的最大值和结果定义之间会出现差异。此外,本文表明,三次谐波电流的相移变化可能会在一侧增加磁场,而在另一侧减少磁场。实际上,这可以帮助避免可能发生野外接触危险的关键方面。