首页> 外文期刊>Electric Power Components and Systems >Harmonic Balance Based Stability Domain Analysis of Period-1 Ferroresonance
【24h】

Harmonic Balance Based Stability Domain Analysis of Period-1 Ferroresonance

机译:基于谐波平衡的1期铁磁谐振的稳定域分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

In an attempt to find regions at risk of ferroresonance, different time-domain simulations and analytical approaches were investigated on a one-phase laboratory transformer. A 2D bifurcation diagram based on a one-term harmonic balance method has been developed. It was shown that increase of core losses during over-voltages significantly affects the stability domain of period-I ferroresonance. Time-domain simulations show that a static core loss model as a function of the maximum flux of the transformer predicts the second bifurcation point with enough accuracy. This modeling approach was incorporated in harmonic balance analysis. A comparison has been made between analysis and measurements.
机译:为了找到存在铁磁化风险的区域,在单相实验室变压器上研究了不同的时域模拟和分析方法。已经建立了基于一阶谐波平衡法的二维分叉图。结果表明,过电压期间铁芯损耗的增加会显着影响I期铁磁谐振的稳定域。时域仿真表明,作为变压器最大通量的函数的静态铁心损耗模型可以足够准确地预测第二分叉点。该建模方法已纳入谐波平衡分析。在分析和测量之间进行了比较。