Power systems measurements are often performed with current and voltage signals derived from instrument transformer secondary circuits. Errors introduced by these transformers are a recognized component of input data errors in supervisory control and data acquisition and phasor measurements. Correcting these errors by in situ calibration is an expensive option; hence, it is seldom employed except in a few special cases. This article proposes a new method for calibrating instrument transformers utilizing phasor measurements by estimating instrument transformers' ratio correctionfactors and phase angle correction factors. The method focuses on the fundamental frequency component of phasor measurements, and, in contrast with some of the techniques proposed in the literature, it does not require accurate instrument transformer models and can be executed as often as needed to keep the calibration up to date. Two alternative calibration techniques are introduced along with the simulation results to prove the feasibility.
机译:电力系统测量通常使用从互感器二次回路中获得的电流和电压信号进行。这些变压器引入的误差是监督控制,数据采集和相量测量中输入数据误差的公认组成部分。通过原位校正来纠正这些错误是一种昂贵的选择。因此,除少数特殊情况外,很少使用。本文提出了一种通过估计互感器的比率校正因子和相角校正因子来利用相量测量来校准互感器的新方法。该方法侧重于相量测量的基本频率分量,并且与文献中提出的某些技术相比,该方法不需要精确的互感器模型,并且可以根据需要经常执行以保持校准最新。介绍了两种替代校准技术以及仿真结果,以证明可行性。