Simple Switching Technique Reduces Inrush Current in Transformers Connected in Parallel

机译:简单的开关技术可降低并联连接的变压器的浪涌电流

获取原文
获取原文并翻译 | 示例

摘要

Many transformers may be connected in parallel to a distribution busbar to supply the load. Restoration of power supply after a black-out is carried out by switching on the transformers one by one, producing high inrush current at the instant of switching of each transformer. It is proposed that circuit breakers connected to all transformer secondaries should be closed first. Then, closing the primary side circuit breaker of the first transformer also energizes all remaining transformers from the secondary side. Inrush current in the first transformer with closed secondary circuit breakers of all transformers does not increase to a very high value. No inrush current is produced during subsequent switching of any other transformer from the primary side, as they are already energized from the secondary side.
机译:许多变压器可能与配电母线并联连接以提供负载。停电后,通过逐个打开变压器来恢复电源,从而在每个变压器切换瞬间产生高浪涌电流。建议与所有变压器次级连接的断路器应首先闭合。然后,闭合第一变压器的初级侧断路器也使次级侧的所有其余变压器通电。所有变压器中具有闭合的次级断路器的第一台变压器中的浪涌电流不会增加到很高的值。在随后从初级侧切换任何其他变压器的过程中,不会产生浪涌电流,因为它们已经从次级侧通电。