首页> 外文期刊>Electric Power Components and Systems >Approximate Model-Free Assessment of Oscillation Stability Determined by the PLLs in a Weakly Grid-Connected Wind Farm with Multiple PMSGs
【24h】

Approximate Model-Free Assessment of Oscillation Stability Determined by the PLLs in a Weakly Grid-Connected Wind Farm with Multiple PMSGs

机译:在具有多个PMSG的弱网状电场中,PLL测定的振荡稳定性的近似模型评估

获取原文
获取原文并翻译 | 示例
           

摘要

The study investigates the oscillation stability determined by phase locked loops (PLLs) in a weakly grid-connected wind farm with multiple permanent magnet synchronous generators (PMSGs). To this end, an equivalent model of the wind farm is derived. Based on the derived equivalent model, the oscillation stability of the wind farm as determined by the dynamics of the PLLs is analytically examined. This paper explains why the PLLs equipped by the PMSGs in the wind farm can lead to instability risk under the condition of weak grid connection. A simple index is proposed to approximately assess instability risk of the wind farm due to the PLLs. The parametric model of the wind farm with the PMSGs is not necessary to calculate the proposed simple index. Hence, it is model-free and applicable in practice when it is difficult to establish the parametric model. An example of a grid-connected wind farm with 12 PMSGs is presented to evaluate and demonstrate the analysis conducted and the simple index proposed in the paper.
机译:该研究研究了在具有多个永磁同步发电机(PMSG)的弱极连接的风电场中通过锁相环(PLL)确定的振荡稳定性。为此,推导出风电场的等效模型。基于派生的等效模型,分析了由PLL的动态确定的风电场的振荡稳定性进行了分析。本文解释了为什么在风电场中的PMSG配备的PLL可以导致弱网格连接条件下的不稳定风险。提出了一种简单的指标,以评估由于PLLS引起的风电场的不稳定风险。使用PMSGS的风电场的参数模型是不需要计算提出的简单索引。因此,当难以建立参数模型时,它在实践中是无模型和适用的。提出了具有12个PMSG的网格连接的风电场的一个例子来评估和展示在纸上提出的分析和简单的指标。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号