Impact of balanced and unbalanced direct current bias on harmonic distortion generated by asymmetric three-phase three-leg transformers

机译:平衡和不平衡直流偏置对非对称三相三桥臂变压器产生的谐波失真的影响

获取原文
获取原文并翻译 | 示例

摘要

The impacts of dc bias and (un)balanced operation including tank effects on harmonic distortions generated by three-phase three-leg transformers are studied. Phase imbalances in power networks can arise from unbalanced loads, imperfections in the transposition of long transmission lines and asymmetry in the structure of transformer cores. When coupled with dc biases, such as those generated by geomagnetically induced currents, the current harmonic distortion in three-phase three-leg transformers can increase significantly. A detailed theoretical study based on electromagnetic theory is performed to explain this phenomenon. A time-domain model of a non-linear three-phase three-leg transformer considering magnetic coupling and core structure asymmetry under (un)balanced dc bias is implemented. Theoretical predictions are confirmed by simulation results which are further supported by experimental tests. The main contribution of this study is a new analysis explaining the link between dc bias and (un)balanced operation on the generation of harmonic distortion in three-phase three-leg transformers.
机译:研究了直流偏置和(非)不平衡运行(包括储能效应)对三相三脚变压器产生的谐波失真的影响。电网中的相位不平衡可能是由不平衡负载,长输电线的换位不完善以及变压器铁芯结构的不对称引起的。当与直流偏置(例如由地磁感应电流产生的偏置)耦合时,三相三桥臂变压器中的电流谐波失真会大大增加。进行了基于电磁理论的详细理论研究来解释这种现象。建立了在(不)平衡直流偏置下考虑磁耦合和铁心结构不对称的非线性三相三脚变压器的时域模型。理论预测由仿真结果证实,并得到实验测试的进一步支持。这项研究的主要贡献是进行了一项新的分析,解释了直流偏置与(不)平衡操作之间的联系,这三相三臂变压器产生了谐波失真。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号