The residual ac breakdown voltage of 6.6 kV dry-cured XLPE power cable under wet-accelerated aging tests

机译:湿加速老化测试下6.6 kV干固化XLPE电力电缆的残余交流击穿电压

获取原文
获取原文并翻译 | 示例
           

摘要

The residual ac breakdown voltage decreased to about half of the initial breakdown voltage after 3 months of accelerated aging test under immersion. This decrease was found to be caused mainly by a trace amount of moisture existing in the insulation. However, the breakdown voltage did not further decrease with increasing moisture content. In order to clarify the influence of moisture, the state of water existing in the insulation was investigated using FTIR (Fourier transform infrared spectroscopy) and optical microscopy. From these results, it was concluded that the moisture in the amorphous region and/or at the interface next to the crystal region caused the reduction of the ac breakdown voltage.