摘要

On line partial discharge (PD) measurements provide information on the dielectric integrity of the High Voltage insulation of oil insulated power transformers during service. These PD measurements are performed using a broadband antenna on an oil valve and UHF detection of PD signals. The sensitivity of this new detection technique is high and immunity for electromagnetic (EM) interference and corona discharges in air outside the transformer is very good. Dielectric faults can be detected in this way in an early stage of development and are classified in four categories. Automatic pattern recognition techniques of phase resolved pulse sequence (PRPS) data are very useful in risk assessment of dielectric faults.
机译:在线局部放电(PD)测量可提供有关维修期间油绝缘电力变压器的高压绝缘的介电完整性的信息。这些PD测量是通过油阀上的宽带天线和PD信号的UHF检测执行的。这种新检测技术的灵敏度很高,并且对变压器外部空气中的电磁(EM)干扰和电晕放电的抗扰性非常好。可以在开发的早期阶段以这种方式检测介电故障,并将其分为四类。相分辨脉冲序列(PRPS)数据的自动模式识别技术在介电故障的风险评估中非常有用。