首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Impact of Weathering on Flashover Performance of Nonceramic Insulators
【24h】

Impact of Weathering on Flashover Performance of Nonceramic Insulators

机译:风化对非陶瓷绝缘子闪络性能的影响

获取原文
获取原文并翻译 | 示例

摘要

Nonceramic (composite) insulators that were in service on 69-230 kV transmission lines for periods up to 25 years were evaluated in the laboratory with the objective of assessing future performance of similar devices in the field. These insulators had housings made from different formulations of silicone rubber and ethylene propylene diene monomer (EPDM) rubber. They were removed from relatively clean locations where weathering was probably the most dominant aging factor. Some EPDM insulators had flashed over during service. Using a combination of scanning electron microscopy (SEM), electrical surface resistance under wet conditions, and a theoretical model for contamination flashover, it has been shown that it is possible to predict the flashover performance in service, based on the thickness of the degraded surface. A threshold value has been established beyond which flashover is likely to occur in the field. This information can be used for planning insulator replacement or maintenance.
机译:在实验室中对在69-230 kV输电线路上使用了长达25年的非陶瓷(复合)绝缘子进行了评估,目的是评估该领域类似设备的未来性能。这些绝缘子的外壳由硅橡胶和乙丙二烯单体(EPDM)橡胶的不同配方制成。将它们从相对清洁的地方移开,在这些地方,风化可能是最主要的老化因素。在维修期间,一些EPDM绝缘子闪过。结合使用扫描电子显微镜(SEM),潮湿条件下的表面电阻和污染物闪络的理论模型,已证明可以根据退化表面的厚度预测使用中的闪络性能。已确定阈值,超过该阈值可能会在现场发生闪络。该信息可用于计划绝缘子的更换或维护。