Lightning impulse voltage and overshoot evaluation proposed in drafts of IEC 60060-1 and future UHV testing

机译:IEC 60060-1草案和未来的超高压测试中提出的雷电冲击电压和过冲评估

获取原文
获取原文并翻译 | 示例
       

摘要

Lightning impulse (LI) voltage testing is an indispensable method for quality assurance of high voltage (HV) and ultra high voltage (UHV) insulation. Not avoidable parasite inductances of the testing circuit provide an oscillation, known as overshoot, at the peak of the lightning impulse (LI). The present paper gives an overview of existing and proposed overshoot evaluation methods of LI voltage. An analytic derivation clarifies the relation between an overshoot magnitude- and overshoot magnitude-/duration- considering method. Hence the finding is derived that both methods provide similar results by applying power transformer testing. Moreover the current paper identifies that a higher permitted overshoot is required for UHV testing by keeping the front time of T1=1.2 ;C;s.
机译:雷电冲击(LI)电压测试是保证高压(HV)和超高压(UHV)绝缘质量的必不可少的方法。测试电路不可避免的寄生电感会在雷电脉冲(LI)的峰值处产生振荡,称为过冲。本文概述了现有和提议的LI电压过冲评估方法。解析推导阐明了超调幅度和超调幅度/持续时间考虑方法之间的关系。因此得出的结论是,两种方法通过应用电源变压器测试都可以提供相似的结果。此外,通过保持T1 = 1.2; C; s的前置时间,当前论文确定了对UHV测试需要更高的允许超调。