In this paper a mathematical model, based on experimentation, to estimate the axial moisture distribution in power transformer windings was developed. The model considers the variables of moisture content in oil, top oil temperature, as well as the transformer's design parameters and ageing of the insulation system. The model was validated using a small-scale experimental setup, which represents a 75 MVA transformer. The developed model proved to be more accurate than existing models. It considers the axial moisture distribution in paper, in 4 thermal zones equidistantly distributed along the height of the winding. This paper compares the results of the proposed model with those provided by other authors.
机译:在实验的基础上,本文建立了一个数学模型来估算变压器绕组中的轴向水分分布。该模型考虑了油中水分含量,最高油温以及变压器的设计参数和绝缘系统老化的变量。该模型已使用代表75 MVA变压器的小规模实验装置进行了验证。事实证明,开发的模型比现有模型更准确。它考虑了纸张中的轴向水分分布,该分布在沿着绕组高度等距分布的4个热区中。本文将提出的模型的结果与其他作者提供的结果进行了比较。