首页> 外文期刊>Dielectrics and Electrical Insulation, IEEE Transactions on >External flashovers, related insulation failures and corrective measures in converter stations of Nelson River bipole 1 and bipole 2
【24h】

External flashovers, related insulation failures and corrective measures in converter stations of Nelson River bipole 1 and bipole 2

机译:尼尔森河双极1和双极2换流站的外部闪络,相关的绝缘故障和纠正措施

获取原文
获取原文并翻译 | 示例
           

摘要

When Bipole 1 was placed in service in the 1970s at +450 kVdc, bushings were found to be vulnerable to external flashovers. Bipole 2 at +500 kVdc in the 1980s had bushings with increased strike distance of 1 m and creepage increased from 32.9 mm/kV to 43.6 mm/kV. This made the Bipole 2 bushings vulnerable to radial puncture under non-uniform wetting. Booster sheds were installed to greatly reduce external flashovers of porcelain bushings in both HVDC bipoles. Recently the porcelain clad, oil filled wall bushings of Bipole 1 have been replaced with oil-free composite wall bushings having silicone rubber sheds.
机译:当Bipole 1在1970年代以+450 kVdc投入使用时,发现套管易受外部闪络的影响。 1980年代+500 kVdc的双极2套管具有增加的触头距离1 m,爬电距离从32.9 mm / kV增加到43.6 mm / kV。这使得Bipole 2衬套在非均匀润湿下容易受到径向刺穿。安装了增压棚,以大大减少两个HVDC双极中瓷套管的外部闪络。近来,Bipole 1的覆瓷,注油的墙壁套管已被具有硅橡胶棚的无油复合墙壁套管所取代。