Free moving metallic particles are one of the most common defects leading to insulation failures in gas insulated substation (GIS) equipment. The present research is designed to diagnose and assess the severity levels of partial discharge (PD) initiated by free moving metallic particles on GIS insulator surface. On a well-established 252 kV GIS experiment platform, long term tests were conducted to observe the entire development process of partial discharge from its very initiation stage till eventual flashover as the applied voltage gradually boosted. Real time measurement was undertaken during the tests to capture the trend curve of partial discharge as a result of test time, scatter plot, histogram, grey-scale map, and time-frequency map of partial discharge. The experimental results indicate that 1) partial discharge provoked by free moving metallic particles in GIS goes through three severity levels, namely, minor discharge, moderate discharge, and threatening discharge; 2) as partial discharge develops, the phase distribution is widening and corresponding shape changes occur in the scatter plot, histogram, grey-scale map, and time-frequency map. It is recommended that the features of phase distribution and the corresponding spectra could be used as important criteria in diagnosing and assessing the severity levels of partial discharge initiated by free moving metallic particles on GIS insulator surface.
机译:自由移动的金属颗粒是导致气体绝缘变电站(GIS)设备绝缘故障的最常见缺陷之一。本研究旨在诊断和评估由GIS绝缘子表面上自由移动的金属颗粒引发的局部放电(PD)的严重程度。在完善的252 kV GIS实验平台上,进行了长期测试,以观察部分放电从其初始阶段一直到最终随着施加电压逐渐升高而发生闪络的整个过程。在测试过程中进行了实时测量,以捕获测试时间,散点图,直方图,灰度图和时频图的结果,以捕获局部放电的趋势曲线。实验结果表明:1)GIS中自由运动的金属颗粒引起的局部放电经历了三个严重程度,即轻微放电,中度放电和威胁放电。 2)随着局部放电的发展,在散点图,直方图,灰度图和时频图中,相位分布变宽,并且形状发生相应变化。建议将相位分布特征和相应的光谱用作诊断和评估由GIS绝缘子表面上自由移动的金属粒子引发的局部放电的严重程度的重要标准。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号