首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Comparison of pd detection methods for power transformers - their sensitivity and characteristics in time and frequency domain
【24h】

Comparison of pd detection methods for power transformers - their sensitivity and characteristics in time and frequency domain

机译:电力变压器PD检测方法的比较-时域和频域的灵敏度和特性

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Partial discharge (PD) detection is an important method for detecting defects in power transformers, and several PD detection methods reported in literature have their respective advantage and disadvantages. In this paper, a simplified PD coupler attached to the tap of the bushing, whose reliability is verified by the EMTP simulation, is proposed in order to extend the application of on-site tap PD detection. Experiments were carried out on 110 kV transformer models to compare the sensitivity of the sensor with some other popular PD detection methods. The characteristics of the detected signals suggest that the proposed coupler has satisfactory sensitivity as well as potential to solve some on-site noise-rejection problems by introduction of ultra-high frequency amplifiers, and thus could be suitable in future for online PD monitoring applications in substations.
机译:局部放电(PD)检测是检测电力变压器缺陷的重要方法,文献中报道的几种PD检测方法各有优缺点。在本文中,提出了一种简化的PD耦合器,该耦合器连接到套管的抽头,其可靠性已通过EMTP仿真得到验证,以扩展现场抽头PD检测的应用。在110 kV变压器模型上进行了实验,以将传感器的灵敏度与其他一些流行的PD检测方法进行比较。检测信号的特性表明,所提出的耦合器具有令人满意的灵敏度以及通过引入超高频放大器解决一些现场噪声抑制问题的潜力,因此将来可能适合于在线PD监测应用中。变电站。