Detection of intense partial discharge of epoxy insulation in sf6 insulated equipment using carbonyl sulfide

机译:使用硫化碳检测SF6绝缘设备中环氧绝缘的强局部放电

获取原文
获取原文并翻译 | 示例
           

摘要

Basin insulators in gas insulated switchgear (GIS) are prone to failure by partial discharge (PD). Insulation diagnosis using gas analysis method has advantages of strong anti-interference ability and high detection precision. This paper reports a new characteristic gas Carbonyl Sulfide (COS) for the detection of PD in epoxy insulators of GIS. The generation of COS is verified by experiments with trace gas detection technique. Experimental results indicate that COS is generated only when the intensity of PD is strong enough to cause flashover on the epoxy insulators. The corresponding production mechanisms of COS have been clarified using quantum chemistry calculations. To assess the PD level using COS, the relationship between discharge power and growth law of the concentration of COS is obtained from the experiments, which indicates that COS could be used as an effective characteristic gas to diagnose epoxy solid insulation of GIS concerning high energy discharge.
机译:气体绝缘开关设备(GIS)中的面盆绝缘子容易因局部放电(PD)而失效。采用气体分析法进行绝缘诊断具有抗干扰能力强,检测精度高的优点。本文报道了一种用于检测GIS环氧绝缘子中PD的新特性气体羰基硫(COS)。通过痕量气体检测技术的实验验证了COS的产生。实验结果表明,只有当PD的强度足以引起环氧绝缘子闪络时,才产生COS。使用量子化学计算已经阐明了COS的相应产生机理。为了通过COS评估PD水平,通过实验得到了放电功率与COS浓度的增长规律之间的关系,表明COS可以作为诊断GIS中涉及高能量放电的环氧固体绝缘的有效特征气体。 。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号