首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Impact of capacitive coupling circuit on online impulse frequency response of a power transformer
【24h】

Impact of capacitive coupling circuit on online impulse frequency response of a power transformer

机译:电容耦合电路对电力变压器在线冲击频率响应的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Detecting the early signs of mechanical failures of power transformer winding is necessary and is possible with online monitoring techniques. Online impulse frequency response analysis (IFRA) is a promising diagnostic method when a transformer is in service. This paper examines the unrevealed problem existing in the method, namely, the impact of bushing capacitive coupling circuit on online impulse frequency response. An equivalent electrical model of capacitive coupling circuit and transformer winding is established. The frequency response of the capacitive coupling circuit is obtained to study its influence on online impulse frequency response. The parameter variations of capacitive coupling circuit caused by coupling capacitance variation and bushing dielectric breakdown are simulated to investigate their influence on online impulse frequency response signatures. A few experiments are eventually performed to verify the theoretical analysis and simulation results. This paper contributes to the application of online IFRA.
机译:检测电力变压器绕组机械故障的早期迹象是必要的,并且可以通过在线监视技术来实现。当变压器投入使用时,在线脉冲频率响应分析(IFRA)是一种很有前途的诊断方法。本文研究了该方法中存在的未公开问题,即套管电容耦合电路对在线脉冲频率响应的影响。建立了电容耦合电路和变压器绕组的等效电气模型。获得了电容耦合电路的频率响应,以研究其对在线脉冲频率响应的影响。模拟了由耦合电容变化和套管介电击穿引起的电容耦合电路的参数变化,以研究其对在线脉冲频率响应信号的影响。最终进行了一些实验,以验证理论分析和仿真结果。本文为在线IFRA的应用做出了贡献。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号