首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >Laboratory investigation of AC corona loss and corona onset voltage on a conductor under icing conditions
【24h】

Laboratory investigation of AC corona loss and corona onset voltage on a conductor under icing conditions

机译:结冰条件下导体上交流电晕损失和电晕起始电压的实验室研究

获取原文
获取原文并翻译 | 示例
       

摘要

Corona losses generated from energized conductors, especially in foul weather conditions, is one of the most important economic factors influencing the design of extra-high voltage (EHV) and ultra-high voltage (UHV) transmission lines. In the present paper, results of laboratory experiments under icing conditions are presented. Two types of ice are considered: rime and glaze. The conditions of ice formation on the test conductor are presented. During the ice accretion, an electric field was applied to the conductor to investigate corona loss and corona onset voltage. The presence of glaze results in a higher corona loss and a lower corona onset voltage compared with rime. The influence of wind velocity and freezing water conductivity were also studied. The test results can help to estimate corona losses of transmission lines in cold climate regions and to improve the design of transmission lines.
机译:通电导体产生的电晕损耗,特别是在恶劣天气条件下,是影响超高压(EHV)和超高压(UHV)传输线设计的最重要的经济因素之一。本文介绍了在结冰条件下的实验室实验结果。考虑两种类型的冰:霜和釉。给出了测试导体上结冰的条件。在积冰期间,向导体施加电场以研究电晕损耗和电晕起始电压。与霜相比,釉的存在导致较高的电晕损失和较低的电晕起始电压。还研究了风速和冷冻水电导率的影响。测试结果可以帮助估算寒冷地区的输电线路电晕损耗,并改善输电线路的设计。