This paper discusses the effect of temperature on polarization and depolarization current measurements on paper oil insulation system. The influence of copper sulphide formed due to corrosive sulphur in mineral oil, on the changes in polarization and depolarization current at different temperatures are considered. A significant increase in the magnitude of polarization and depolarization currents due to deposits of copper sulphide on paper layers is observed. The conductivity of paper insulation increases significantly with increase in temperature. The increase in current is attributed to thermally active conducting particles of copper sulphide. The Debye model parameters of equivalent circuit under copper corrosion have been computed and a model for failure due to copper sulphide is explained using the data on polarization and depolarization currents.
机译:本文讨论了温度对纸绝缘油系统极化和去极化电流测量的影响。考虑了矿物油中的腐蚀性硫形成的硫化铜对不同温度下极化和去极化电流变化的影响。观察到由于硫化铜在纸层上的沉积,极化电流和去极化电流的大小显着增加。纸绝缘的电导率随温度的升高而显着增加。电流的增加归因于硫化铜的热活性导电颗粒。计算了铜腐蚀下等效电路的德拜模型参数,并使用极化电流和去极化电流数据解释了硫化铜导致的失效模型。